ML
    • Recent
    • Categories
    • Tags
    • Popular
    • Users
    • Groups
    • Register
    • Login

    Cabling and firecode

    IT Discussion
    6
    17
    1.3k
    Loading More Posts
    • Oldest to Newest
    • Newest to Oldest
    • Most Votes
    Reply
    • Reply as topic
    Log in to reply
    This topic has been deleted. Only users with topic management privileges can see it.
    • syko24S
      syko24
      last edited by

      If you are running cat5e/cat6 above a drop ceiling and need to cut a hole in the drywall to drop the cable down to the mudring below do you need to have a sleeve or piece of conduit to meet firecode? Or can you drop your cable and fill the hole with fire rate caulk? I know codes are different depending on your area but was just curious what the proper method would be generally speaking.

      1 Reply Last reply Reply Quote 0
      • coliverC
        coliver
        last edited by coliver

        It depends on your location. You can check with your local code enforcer, if they are competent. Around here as long as the cable is plenum rated it doesn't need to be in a conduit, although I would generally put it in one so I can easily add more cables if need be.

        syko24S 1 Reply Last reply Reply Quote 4
        • wirestyle22W
          wirestyle22
          last edited by wirestyle22

          Technically you're supposed to be an eletrician in NJ to run low voltage cabling. Seems dumb to me. No one here (in my state) does it.The guy who is contracted by the state here just does voip and is most definitely not an electrician. No one seems to care.

          coliverC 1 Reply Last reply Reply Quote 0
          • syko24S
            syko24 @coliver
            last edited by

            @coliver Thanks for the reply.

            I have seen cases where the installer sometimes just bends a piece of conduit at the top of the drywall but doesn't run the conduit down to the box. I assume this is because there was not the room or desire to rip open the wall completely to run the conduit.

            coliverC 1 Reply Last reply Reply Quote 0
            • coliverC
              coliver @wirestyle22
              last edited by

              @wirestyle22 said in Cabling and firecode:

              Technically you're supposed to be an eletrician in NJ to run low voltage cabling. Seems dumb to me. No one here (in my state) does it.The guy who is contracted by the state here just does voip and is most definitely not an electrician. No one seems to care.

              That's the new fight in NY... especially with LED lights that can run off of a cheap PoE switch. We have our networking students doing some of that in a few locations now.

              1 Reply Last reply Reply Quote 1
              • coliverC
                coliver @syko24
                last edited by

                @syko24 said in Cabling and firecode:

                @coliver Thanks for the reply.

                I have seen cases where the installer sometimes just bends a piece of conduit at the top of the drywall but doesn't run the conduit down to the box. I assume this is because there was not the room or desire to rip open the wall completely to run the conduit.

                That is probably the case but as long as the cable is plenum rated then you're probably fine. But I would check with your local code enforcer just to be sure.

                DashrenderD 1 Reply Last reply Reply Quote 0
                • DashrenderD
                  Dashrender @coliver
                  last edited by

                  @coliver said in Cabling and firecode:

                  @syko24 said in Cabling and firecode:

                  @coliver Thanks for the reply.

                  I have seen cases where the installer sometimes just bends a piece of conduit at the top of the drywall but doesn't run the conduit down to the box. I assume this is because there was not the room or desire to rip open the wall completely to run the conduit.

                  That is probably the case but as long as the cable is plenum rated then you're probably fine. But I would check with your local code enforcer just to be sure.

                  What does plenum rating have to do with going down the wall? Most places don't allow you to run non plenum rated in plenum spaces, but if his drop seeing isn't a plenum (air return space) and is instead ducted, then he shouldn't need plenum rated cable.

                  coliverC 1 Reply Last reply Reply Quote 0
                  • coliverC
                    coliver @Dashrender
                    last edited by coliver

                    @Dashrender said in Cabling and firecode:

                    @coliver said in Cabling and firecode:

                    @syko24 said in Cabling and firecode:

                    @coliver Thanks for the reply.

                    I have seen cases where the installer sometimes just bends a piece of conduit at the top of the drywall but doesn't run the conduit down to the box. I assume this is because there was not the room or desire to rip open the wall completely to run the conduit.

                    That is probably the case but as long as the cable is plenum rated then you're probably fine. But I would check with your local code enforcer just to be sure.

                    What does plenum rating have to do with going down the wall? Most places don't allow you to run non plenum rated in plenum spaces, but if his drop seeing isn't a plenum (air return space) and is instead ducted, then he shouldn't need plenum rated cable.

                    That's true riser may be fine in this instance. Generally anything above a drop ceiling is often plenum space in an office building. So he would need the plenum rating for that area.

                    DashrenderD 1 Reply Last reply Reply Quote 1
                    • DashrenderD
                      Dashrender @coliver
                      last edited by

                      @coliver said in Cabling and firecode:

                      @Dashrender said in Cabling and firecode:

                      @coliver said in Cabling and firecode:

                      @syko24 said in Cabling and firecode:

                      @coliver Thanks for the reply.

                      I have seen cases where the installer sometimes just bends a piece of conduit at the top of the drywall but doesn't run the conduit down to the box. I assume this is because there was not the room or desire to rip open the wall completely to run the conduit.

                      That is probably the case but as long as the cable is plenum rated then you're probably fine. But I would check with your local code enforcer just to be sure.

                      What does plenum rating have to do with going down the wall? Most places don't allow you to run non plenum rated in plenum spaces, but if his drop seeing isn't a plenum (air return space) and is instead ducted, then he shouldn't need plenum rated cable.

                      That's true riser may be fine in this instance. Generally anything above a drop ceiling is often plenum space in an office building. So he would need the plenum rating for that area.

                      My experience has been closer to 50/50. For example, my current building is all ducted.

                      coliverC 1 Reply Last reply Reply Quote 0
                      • coliverC
                        coliver @Dashrender
                        last edited by coliver

                        @Dashrender said in Cabling and firecode:

                        @coliver said in Cabling and firecode:

                        @Dashrender said in Cabling and firecode:

                        @coliver said in Cabling and firecode:

                        @syko24 said in Cabling and firecode:

                        @coliver Thanks for the reply.

                        I have seen cases where the installer sometimes just bends a piece of conduit at the top of the drywall but doesn't run the conduit down to the box. I assume this is because there was not the room or desire to rip open the wall completely to run the conduit.

                        That is probably the case but as long as the cable is plenum rated then you're probably fine. But I would check with your local code enforcer just to be sure.

                        What does plenum rating have to do with going down the wall? Most places don't allow you to run non plenum rated in plenum spaces, but if his drop seeing isn't a plenum (air return space) and is instead ducted, then he shouldn't need plenum rated cable.

                        That's true riser may be fine in this instance. Generally anything above a drop ceiling is often plenum space in an office building. So he would need the plenum rating for that area.

                        My experience has been closer to 50/50. For example, my current building is all ducted.

                        Fair enough... also why @syko24 should talk to their code enforcer.

                        syko24S 1 Reply Last reply Reply Quote 2
                        • syko24S
                          syko24 @coliver
                          last edited by

                          @coliver said in Cabling and firecode:

                          @Dashrender said in Cabling and firecode:

                          @coliver said in Cabling and firecode:

                          @Dashrender said in Cabling and firecode:

                          @coliver said in Cabling and firecode:

                          @syko24 said in Cabling and firecode:

                          @coliver Thanks for the reply.

                          I have seen cases where the installer sometimes just bends a piece of conduit at the top of the drywall but doesn't run the conduit down to the box. I assume this is because there was not the room or desire to rip open the wall completely to run the conduit.

                          That is probably the case but as long as the cable is plenum rated then you're probably fine. But I would check with your local code enforcer just to be sure.

                          What does plenum rating have to do with going down the wall? Most places don't allow you to run non plenum rated in plenum spaces, but if his drop seeing isn't a plenum (air return space) and is instead ducted, then he shouldn't need plenum rated cable.

                          That's true riser may be fine in this instance. Generally anything above a drop ceiling is often plenum space in an office building. So he would need the plenum rating for that area.

                          My experience has been closer to 50/50. For example, my current building is all ducted.

                          Fair enough... also why @syko24 should talk to their code enforcer.

                          Totally agree with checking on code. I guess my question was more for personally knowledge. I've seen cablers do things differently from job to job and was just curious what was best practice. Or when hiring someone to cable I can be more knowledgeable.

                          DashrenderD 1 Reply Last reply Reply Quote 0
                          • DashrenderD
                            Dashrender @syko24
                            last edited by

                            @syko24 said in Cabling and firecode:

                            @coliver said in Cabling and firecode:

                            @Dashrender said in Cabling and firecode:

                            @coliver said in Cabling and firecode:

                            @Dashrender said in Cabling and firecode:

                            @coliver said in Cabling and firecode:

                            @syko24 said in Cabling and firecode:

                            @coliver Thanks for the reply.

                            I have seen cases where the installer sometimes just bends a piece of conduit at the top of the drywall but doesn't run the conduit down to the box. I assume this is because there was not the room or desire to rip open the wall completely to run the conduit.

                            That is probably the case but as long as the cable is plenum rated then you're probably fine. But I would check with your local code enforcer just to be sure.

                            What does plenum rating have to do with going down the wall? Most places don't allow you to run non plenum rated in plenum spaces, but if his drop seeing isn't a plenum (air return space) and is instead ducted, then he shouldn't need plenum rated cable.

                            That's true riser may be fine in this instance. Generally anything above a drop ceiling is often plenum space in an office building. So he would need the plenum rating for that area.

                            My experience has been closer to 50/50. For example, my current building is all ducted.

                            Fair enough... also why @syko24 should talk to their code enforcer.

                            Totally agree with checking on code. I guess my question was more for personally knowledge. I've seen cablers do things differently from job to job and was just curious what was best practice. Or when hiring someone to cable I can be more knowledgeable.

                            People do illegal things all the time. All you can do it reach out to the highest authority on the matter to ensure something's being done to law if that's important to you.
                            or have clauses in your contract that specifically state the liability of the installer if it's not done to code.

                            syko24S 1 Reply Last reply Reply Quote 1
                            • syko24S
                              syko24 @Dashrender
                              last edited by

                              @Dashrender - I think low voltage is one of those things that a lot of installers cut corners on because most people aren't going to check their work above the ceilings or down the walls. The client typically just cares that the jacks work and that's it.

                              DashrenderD 1 Reply Last reply Reply Quote 1
                              • DashrenderD
                                Dashrender @syko24
                                last edited by

                                @syko24 said in Cabling and firecode:

                                @Dashrender - I think low voltage is one of those things that a lot of installers cut corners on because most people aren't going to check their work above the ceilings or down the walls. The client typically just cares that the jacks work and that's it.

                                Are you implying that the client will check other things? Like power wires, etc? I highly doubt it.

                                travisdh1T syko24S 2 Replies Last reply Reply Quote 0
                                • JaredBuschJ
                                  JaredBusch
                                  last edited by

                                  @syko24 National electrical code requires that any penetration of a fire wall be sealed.

                                  You know it is a fire wall if both sides are dry walled up.

                                  Whether or not you have to use a pipe to penetrate will be based on state and local codes.

                                  1 Reply Last reply Reply Quote 2
                                  • travisdh1T
                                    travisdh1 @Dashrender
                                    last edited by

                                    @Dashrender said in Cabling and firecode:

                                    @syko24 said in Cabling and firecode:

                                    @Dashrender - I think low voltage is one of those things that a lot of installers cut corners on because most people aren't going to check their work above the ceilings or down the walls. The client typically just cares that the jacks work and that's it.

                                    Are you implying that the client will check other things? Like power wires, etc? I highly doubt it.

                                    Oh, please, don't get me started on that topic! I had to move four people in the FEA group thanks to sloppy/lazy cable runs being put in. At the time they "only" had 3 different workstations with 21" CRT tubes for each of them... not much space was left on the desk after all their equipment was setup.

                                    1 Reply Last reply Reply Quote 0
                                    • syko24S
                                      syko24 @Dashrender
                                      last edited by

                                      @Dashrender said in Cabling and firecode:

                                      @syko24 said in Cabling and firecode:

                                      @Dashrender - I think low voltage is one of those things that a lot of installers cut corners on because most people aren't going to check their work above the ceilings or down the walls. The client typically just cares that the jacks work and that's it.

                                      Are you implying that the client will check other things? Like power wires, etc? I highly doubt it.

                                      No but cabling and recabling is sometimes done after buildout of an office. No inspector checking the work.

                                      1 Reply Last reply Reply Quote 0
                                      • 1 / 1
                                      • First post
                                        Last post